Driver setup guide
For our PLC programming cables (Mitsubishi FX, Delta DVP, Siemens S7-200) and the USB-RS485 converter. Takes about 10 minutes.
Panduan pasang driver untuk kabel program PLC dan penukar USB-RS485. Lebih kurang 10 minit.
1. Find your cable's chip
Each cable uses one of three chips, and each chip has its own driver.
- Plug the cable into a USB port on your laptop. Do not connect the PLC yet.
- Press Windows + X and choose Device Manager.
- Open Ports (COM & LPT). If it is not there, open Other devices.
- Match the cable's name with the table below.
| Name in Device Manager | Chip | VID code |
|---|---|---|
| USB-SERIAL CH340 (COM3) | CH340 | VID_1A86 |
| USB Serial Port (COM4) | FTDI FT232 | VID_0403 |
| Prolific USB-to-Serial Comm Port (COM5) | Prolific PL2303 | VID_067B |
See a yellow triangle? The driver is not installed yet. Right-click the name, choose Properties, open the Details tab, pick Hardware Ids, and match the VID code with the table.
Buka Device Manager (Windows + X) dan padankan nama atau kod VID untuk kenal pasti cip.
2. Install the driver
Windows 10 and 11 usually install the driver by themselves within 1-2 minutes when online. If Device Manager already shows the full name with a COM number, skip to step 3.
Download drivers only from the chip maker's official site below. Other driver sites sometimes bundle malware.
CH340
- Open the official WCH page and download CH341SER.EXE (it covers the CH340 too).
- Run it, click INSTALL, and wait for the success message.
- Unplug the cable, wait 5 seconds, plug it back in. You should see USB-SERIAL CH340 (COMx).
FTDI FT232
- Open the official FTDI page and, in the Windows row, download the setup executable.
- Run it and follow the steps to the end.
- Unplug and replug the cable. You should see USB Serial Port (COMx).
Prolific PL2303
- Open the official Prolific site and find the PL2303 Windows Driver.
- Download and install it, then unplug and replug the cable.
- You should see Prolific USB-to-Serial Comm Port (COMx).
See Code 10 or "PL2303HXA PHASED OUT"? Newer Prolific drivers refuse some older chips. Do not try drivers from other sites. Contact us and we will help or replace your cable.
Windows biasanya pasang driver sendiri. Jika tidak, muat turun hanya dari laman rasmi pembuat cip, kemudian cabut dan cucuk semula kabel.
3. Find the COM port
The COM number is at the end of the cable's name in Device Manager, for example COM3. Your PLC software needs it.
Higher than 9 (for example COM12)? Older software such as GX Developer and MicroWIN may not see it. Change it to a low number:
- Right-click the cable's name and choose Properties.
- Open Port Settings and click Advanced.
- Under COM Port Number, pick a low number not marked "in use". Click OK, then unplug and replug.
Use the same USB port each time; another port can get a different COM number.
Catat nombor COM. Jika melebihi 9, tukar di Properties, Port Settings, Advanced.
4. Connect your software
Connect the cable to the PLC, power the PLC on, then follow the steps for your software.
Mitsubishi FX: GX Works2
- In the left panel, open Connection Destination and double-click Connection1.
- PC side I/F: double-click Serial USB, choose RS-232C, your COM number and 9.6 kbps.
- PLC side I/F: choose PLC Module, then click Connection Test.
GX Developer: Online > Transfer setup, double-click Serial, pick the COM number, click Connection test.
Delta DVP: WPLSoft or ISPSoft
- WPLSoft: Options > Communication Settings, Transmission Type: RS232, pick the COM number.
- Click Auto-detect if it is there. If not: 9600, 7, Even, 1, ASCII, Station Address 1.
- ISPSoft: open COMMGR, click Add, choose Driver Type: RS232 and the COM number, then OK and Start. In ISPSoft, open Tools > Communication Settings.
Siemens S7-200: STEP 7-MicroWIN
- Click Set PG/PC Interface, choose PC/PPI cable (PPI), click Properties.
- PPI tab: Address 0, 9.6 kbps. Local Connection tab: pick your COM number, not USB.
- Open Communications and double-click Double-Click to Refresh.
USB-RS485 converter: Modbus Poll
- Wiring: A+ to the device's A or D+, B- to B or D-, and GND if the device has one.
- Connection > Connect: your COM number, Mode: RTU, and the same baud rate, parity and stop bits as the device (often 9600, 8, None, 1).
- Setup > Read/Write Definition: the slave ID, function and register address from the device manual. No reply? Swap A and B.
Sambung PLC, hidupkan, dan pilih nombor COM dalam tetapan komunikasi software. Untuk RS485, padankan tetapan peranti dan tukar A/B jika tiada respons.
5. Common problems
- The cable does not show up in Device Manager
- Try another USB port. Plug straight into the laptop, not a USB hub.
- Yellow triangle, Code 10 or Code 28
- Reinstall the driver for your chip (step 2). Prolific Code 10: contact us.
- The software says "cannot communicate" or "timeout"
- Check the COM number in the software matches Device Manager. Close other programs using the same COM port.
- The software does not list the COM port
- Change it to a low COM number (step 3), then reopen the software.
- Connects, then drops
- Push the plug firmly into the PLC. Lower the speed to 9.6 kbps.
- No data from an RS485 device
- Swap the A and B wires. Check the slave ID, baud rate and parity match the device.
Still stuck? Send us your PLC model, Windows version, software name, and screenshots of Device Manager and the error. We help until it works, and replace the cable if it is faulty.